串联补燃型吸收式换热机组最大供热能力分析
CSTR:
作者:
作者单位:

(1.哈尔滨工业大学 建筑学院 哈尔滨 150006; 2.寒地城乡人居环境科学与技术工业 和信息化部重点实验室(哈尔滨工业大学),哈尔滨 150009)

作者简介:

张承虎(1980—),男,副教授

通讯作者:

廉雪丽,lianxueli150@163.com

中图分类号:

TK11

基金项目:

中央高校基本科研业务费专项资金(HIT.NSRIF.2017056)


Analysis of maximum heating capacity of series-type supplemental fired absorption heat exchanger
Author:
Affiliation:

(1.School of Architecture, Harbin Institute of Technology, Harbin 150006, China; 2.Key Laboratory of Cold Region Urban and Rural Human Settlement Environment Science and Technology, Ministry of Industry and Information Technology (Harbin Institute of Technology), Harbin 150009, China)

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    为进一步降低供热热力站一次侧的回水温度,增大供热量,采用串联补燃型吸收式换热机组代替常规单段吸收式换热机组. 在仅考虑可行性传热端差的技术制约条件下,通过分析串联补燃型吸收式换热机组内各传热部件的热力循环过程及传热过程,建立机组的数学模型并采用迭代的数值方法进行求解,定量分析了在满足换热站设计要求的一次侧供水温度,二次侧供、回水温度条件下,一次侧回水最低温度、机组最大供热能力以及机组内换热量的分配规律. 研究结果表明:在一次侧供水温度为110 ℃,二次侧供、回水温度为60/45 ℃时,串联补燃型吸收式换热机组的一次侧回水最低温度为22 ℃,管网输送能力是传统110/60 ℃水-水板式换热器的1.76倍,供热量是传统水-水板式换热器的2倍;对于常规单段吸收式换热机组而言,一次侧和二次侧的供水温度对其扩大系数基本没有影响,其值约为1.5. 在一次侧供水温度为100 ℃,二次侧供、回水温度为69℃/54℃时,补燃型吸收式换热机组的扩大系数最大约为3.3.

    Abstract:

    To further reduce the outlet temperature of the primary water and increase the transmission capacity of the heating pipe network, the series-type supplemental fired absorption heat exchanger was used at the heat station of central heating system to replace the conventional single-segment absorption heat exchanger. In this study, with the technical constraints of feasibility of heat transfer terminal difference considered only, by analyzing the heat transfer process and thermodynamic cycle of each heat transfer component in series-type supplemental fired absorption heat exchanger, the mathematical model of the unit was established and solved by iterative numerical method, and the temperature conditions of primary water inlet, secondary water inlet and outlet satisfying the design requirements of heat exchanger station were quantitatively analyzed. The distribution rules of the minimum temperature of primary water outlet, the maximum heat supply of unit, and the heat transfer in unit were discussed. Research results show that when the temperatures of the primary water inlet was 110℃, the secondary water inlet and outlet were 60/45 ℃, the minimum temperature of the primary water outlet of the supplemental heat exchange unit was 22 ℃. The conveying capacity of the pipe network was 1.76 times of a conventional 110/60 ℃ water-to-water heat exchanger and the heat supply was twice of a conventional water-water heat exchanger. For conventional single-stage absorption heat exchangers, the primary and secondary water supply temperatures had little effects on the expansion coefficient, which was about 1.5. When the primary water inlet temperature was 100 ℃ and the secondary water inlet/outlet temperature was 69/54 ℃, the maximum expansion coefficient of the supplementary combustion absorption heat exchanger was about 3.3.

    参考文献
    相似文献
    引证文献
引用本文

张承虎,廉雪丽,李亚平.串联补燃型吸收式换热机组最大供热能力分析[J].哈尔滨工业大学学报,2019,51(10):164. DOI:10.11918/j. issn.0367-6234.201804061

复制
相关视频

分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2018-04-10
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2019-10-17
  • 出版日期: