热风极片耦合的湿涂层热质传递数理模型
CSTR:
作者:
作者单位:

(华东交通大学土木建筑学院,南昌 330013)

作者简介:

王佳骏(2000—),男,硕士研究生;麻宏强(1984—),男,教授,博士生导师

通讯作者:

曾月,yuyan116@qq.com;麻宏强,mahq2014@sina.com

中图分类号:

TB61

基金项目:

国家自然科学基金(52368071);江西省创新领军人才项目(jxsq2023101064,jxsq2023102132);江西省2023年度研究生创新专项资金(YC2023-S486)


Mathematical model of heat and mass transfer in wet coating coupled with hot air and electrode plate
Author:
Affiliation:

(School of Civil Engineeringand Architecture, East China Jiaotong University, Nanchang 330013, China)

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    为解决对流干燥过程中极片湿涂层热质传递过程数值计算复杂的问题,综合考虑热风和基材铝板对湿涂层热质传递特性的共同影响,基于多孔介质多场耦合理论,采用无网格并行方法建立三维热风极片湿涂层热质传递数理模型,提出湿涂层热质传递过程的差分计算方法。由于数理模型对计算精度要求较高,模拟计算时间长,为提高计算效率,基于相似理论提出缩尺模拟方法,并通过对比不同缩尺比例湿涂层的温、湿度变化规律验证其可靠性。结果表明:不同缩尺比例下湿涂层湿度判定系数R2均大于0.99;原尺模型的模拟时间为5 h,缩尺倍数为800的缩尺模型的模拟计算时间为2.77 h,相比原尺模型减少了44.6%,有效提高了数值计算效率。最后,基于缩尺模拟方法对数理模型进行可靠性验证,结果表明,热风极片湿涂层热质传递数理模型温、湿度模拟结果与实验数据的误差均在±15%以内,仅个别数据点偏大,说明该模型具有可靠性。

    Abstract:

    In order to address the complex numerical calculations of the heat and mass transfer processes in the wet coating of electrode plates during convective drying, this study comprehensively considers the combined effects of hot air and the aluminum substrate on the thermal and mass transfer characteristics of the wet coating. Based on the multi-field coupling theory in porous media, a three-dimensional mathematical model of heat and mass transfer in the hot air-electrode plate wet coating is established using a meshless parallel method. Meanwhile, a difference calculation method for the heat and mass transfer process in the wet coating is proposed. Due to the high requirements for computational accuracy in mathematical model, a scale simulation method based on similarity theory is proposed to improve computational efficiency. The reliability of this method is validated through the comparison of temperature and humidity variations of wet coatings at different scaling ratios. The results show that the determination coefficient R2 of humidity assessment of the wet coating at different scaling ratios is greater than 0.99. The simulation time for the original-scale model is 5 hours, while the simulation time for the scaled model with a scaling factor of 800 is 2.77 hours, representing a 44.6% reduction compared to the original model, thus effectively improving the numerical computation efficiency. Finally, the reliability of mathematical model is validated based on scale simulation method. The results show that the simulation temperature and humidity values from the hot air-electrode plate wet coating heat and mass transfer model have errors within ±15% of the experimental data, with only a few data points exhibiting slightly larger discrepancies, indicating that the model is reliable.

    参考文献
    相似文献
    引证文献
引用本文

王佳骏,曾月,麻宏强,谢越,王圣寻.热风极片耦合的湿涂层热质传递数理模型[J].哈尔滨工业大学学报,2025,57(5):77. DOI:10.11918/202403028

复制
相关视频

分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2024-03-11
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2025-06-10
  • 出版日期:
文章二维码