Contrast experiments on three different types of underground heat exchangers of GSHP system
CSTR:
Author:
Affiliation:

(1.Key Laboratory of the Three Gorges Reservoir Region’s Eco-Environment(Chongqing University), Ministry of Education, 400045 Chongqing, China; 2.China Southwest Architectural Design and Research Institute Co.,Ltd. 610041Chengdu, China)

Clc Number:

TK02

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    Based on the deficiencies of existing ground heat exchangers, a new type energy-storage heat exchanger is proposed, which consists of three inlet pipes and one thermal insulation outlet pipe. Thermal resistance of this new type heat exchanger is calculated, which shows a much smaller value over conventional ones. Experimental measurements to evaluate the performance of single-U, double-U and the new design, were carried out in boreholes about 96 meters deep, which showed superior performance of the new type. The thermal resistance of the new type was 29%-34% and 10%-15% smaller than that of single-U and double-U respectively. The circulation water temperature rise of new type was 1.5 ℃ lower than double-U.