Please submit manuscripts in either of the following two submission systems

    ScholarOne Manuscripts

  • ScholarOne
  • 勤云稿件系统

  • 登录

Search by Issue

  • 2024 Vol.31
  • 2023 Vol.30
  • 2022 Vol.29
  • 2021 Vol.28
  • 2020 Vol.27
  • 2019 Vol.26
  • 2018 Vol.25
  • 2017 Vol.24
  • 2016 vol.23
  • 2015 vol.22
  • 2014 vol.21
  • 2013 vol.20
  • 2012 vol.19
  • 2011 vol.18
  • 2010 vol.17
  • 2009 vol.16
  • No.1
  • No.2

Supervised by Ministry of Industry and Information Technology of The People's Republic of China Sponsored by Harbin Institute of Technology Editor-in-chief Yu Zhou ISSNISSN 1005-9113 CNCN 23-1378/T

期刊网站二维码
微信公众号二维码
Related citation:Xiaofei Lu,Zhiwei Zhou,Ming Zhuang,Lilong Qiu.Process Modeling and Control Simulation for a 500W@4.5K Helium Refrigerator[J].Journal of Harbin Institute Of Technology(New Series),2016,23(4):15-21.DOI:10.11916/j.issn.1005-9113.2016.04.003.
【Print】   【HTML】   【PDF download】   View/Add Comment  Download reader   Close
←Previous|Next→ Back Issue    Advanced Search
This paper has been: browsed 1361times   downloaded 887times 本文二维码信息
码上扫一扫!
Shared by: Wechat More
Process Modeling and Control Simulation for a 500W@4.5K Helium Refrigerator
Author NameAffiliation
Xiaofei Lu Institute of Plasma Physics, Chinese Academy of Sciences, Hefei 230031, China 
Zhiwei Zhou Institute of Plasma Physics, Chinese Academy of Sciences, Hefei 230031, China 
Ming Zhuang Institute of Plasma Physics, Chinese Academy of Sciences, Hefei 230031, China 
Lilong Qiu Institute of Plasma Physics, Chinese Academy of Sciences, Hefei 230031, China 
Abstract:
In order to investigate dynamic behaviors of a 500W@4.5K helium refrigerator,the process simulator has been completed. The cryogenic process model is described and main components are customized.The real-time communication between the process model and the control system has been achieved.Compared with the preliminary experimental data, the errors of temperatures during the process of 300 K-80 K are less than 10%. The process model is validated to predict the cool-down process very well. The controller parameters are tuned in simulation and applied to the actual refrigerator suitably.Based on the dynamic simulation, the operation of Joule-Thomson(JT) by pass valve has been optimized. And the cool-down process from 300 K to 4.5 K has been simulated under the control programs . Simulation results indicate that this dynamic simulator based on actual control architecture is available to process control and operation optimization for the helium refrigerators.
Key words:  Helium refrigerator  process simulation  controller tuning  operation optimization  virtual commissioning